The report covers three full-scale fire tests in a mobile steel shelving storage system containing archival storage. The storage module, consisting of rows of mobile steel shelving, was 35 feet long, 20.5 feet wide and 7.75 feet high. Fire protection was provided by standard 1/2 inch automatic sprinklers, temperature rated at 280 F and installed on a spacing of 10 feet x 10 feet. Water pressure was automatically controlled to produce a constant discharge density of 0.30 gpm/ft.


    Zugriff

    Zugriff über TIB

    Verfügbarkeit in meiner Bibliothek prüfen


    Exportieren, teilen und zitieren



    Titel :

    Fire Tests in Mobile Storage Systems for Archival Storage